1. Which of the following is unique to the commissioning of hospital and laboratory ventilation systems?
A) Room air pressure requirements
B) Verification of maximum energy efficiency
C) The role of hospitals and laboratories in community disasters
D) System interoperability
2. Which of the following particles has the smallest aerodynamic diameter?
A) Outdoor fungal spores
B) Virus
C) Bacteria
D) Indoor fungal spores
3. If 10,000 cfm (4,740 L/s) of air is cooled from 80°F (26.7°C) to 55°F (12.8°C) at sea level, what is the sensible heat transfer rate?
A) 93.75 tons (329.6 kW)
B) 22.5 tons (79.1 kW)
C) 270 BTUH (79.1 W)
D) 1125 BTUH (329.6 W)
4. In accordance with ASHRAE Standard 170, the pressure differential in which of the following rooms shall be continuously monitored?
A) Isolation Room
B) Patient Room
C) Recovery Room
D) Procedure Room
5. Which of the following equipment rooms would MOST appropriately be controlled to be positive to adjacent spaces?
A) Electrical
B) Boiler
C) Refrigeration
D) Telecommunications